Classic 40

Portable Cooling Contact: 508.460.0904 x3

Electronic Features
Control Panel
Digital
Thermostat Control Electronic
Cooling Capacity
Rating Conditions: 95°F at 60% RH
39,000 Btu/h
Electrical
Characteristics
Voltage Requirement
3 Phase, 220V
Total Power Consumption 4.2 kW
Current Consumption 14 amps
Recommended Fuse Size 25 amps
NEMA Plug Configuration L15-30
Min. Max. Voltage 198 – 240
Fans
Motor Output
0.75 kW Evap.
0.40 kW Cond.
Evaporator
Fan Type
Centrifugal
Max.Air Flow high/low 1060 CFM
Max. External Static Pressure 1.73 IWG
Condenser
Fan Type
Propeller
Max. Air Flow high/low 2650 CFM
Max. External Static Pressure 0.05 IWG
Compressor
Type
Hermetic Scroll
Output 2.3 kW
Refrigerant
R-410A
3.9 lb
Dimensions
W x D x H
26 x 44 x 38 in
Net Weight/
Shipping Weight
 
344/396 lb
Power Cord
Gauge
12 AWG (4-core)
Length 6 ft
Condensate
Tank Capacity
 
2 @ 5 gal (Optional)
Operating Conditions
Min. Max. (@ 50% RH)
75° – 115°F
Max. Duct
Length
Per Cold Duct Hose
Varies
Hot Duct Hose 40 ft
Max.
Sound Level
With Condenser – Duct high/low
N/A
Without Condenser – Duct high/low 72 dB(A)