Climate Pro 18

Portable Cooling Contact: 508.460.0904 x3

Electronic Features
Control
Programmable
Cooling Capacity
Rating Conditions:
Cooling: 80°F, 50% RH Indoor & Outdoor
Heating: 70°F, 57% RH Indoor
                 47°F,  70% RH Outdoor
Cooling: 14,600 Btu/h
Heating: 13,700 Btu/h
Electrical Characteristics
Voltage Requirement
1 Phase, 115V
Total Power Consumption Cooling: 1.54 kW, Heating: 1.61 kW
Current Consumption Cooling: 14.1 amps, Heating: 14.7 amps
Recommended Fuse Size 20 amps
NEMA Plug Configuration 5 – 20P
Min. – Max. Voltage 105 – 125
Fans
Motor Output – high/mid/low
Supply: 0.12/0.045/0.017 kW
Exhaust: 0.135 kW
Indoor Heat Exchanger (Supply)
Fan Type
Centrifugal
Max. Air Flow – high/mid/low 540/440/350 CFM
Max. External Static Pressure 0.31 IWG
Outdoor Heat Exchanger (Exhaust)
Fan Type
Centrifugal
Max. Air Flow 700 CFM
Max. External Static Pressure 0.23 IWG
Compressor
Type
Hermetic Rotary
Output 1.16 kW
Refrigerant
Type
R-410A
Dimensions
W x D X H
21 x 27 x 49 in
Net Weight/Shipping Weight
214/257 lb
Power Cord
Gauge
12 AWG (3-core)
Length 10 ft
Condensate Tank Capacity
5 gal
Operating Conditions
Min. – Max. (@ 50% RH)
Cooling: 65° – 95°F
Heating:
Without Plenum:
40°F – 80°F (Air entering indoor and outdoor heat exchangers)
With Plenum:
40°F – 80°F (Air entering indoor heat exchanger)
24°F- 80°F (Air entering outdoor heat exchanger)
Max. Equivalent Duct Length
Supply Duct Hose
25 ft
Exhaust Duct Hose 100 ft
Max. Sound Level
With Exhaust Duct – high/low
61/59 dB(A)
Without Exhaust Duct – high/low 62/60 dB(A)