Climate Pro K24

Climate Pro K24Two tons of worry-free, on-the-spot cooling.

With a space-saving footprint of slightly more than 4 sq. ft., the Climate Pro K24 provides up to 24,000 Btu/h of cooling relief—helping keep employees productive and preventing electronics from overheating.

  • Modest power usage. Runs on 208/230V 20 amp circuit and consumes 2.9 kW.
  • Cooling support effective in conditions from 65° to 95°F.

Portable Cooling Contact: 508.460.0904 x3

Features


Electronic Features

Control PanelProgrammable

Cooling Capacity

Rating Conditions: 95°F @ 60% RH @ 208/230V24,000 Btu/h

Electrical Characteristics

Voltage Requirement (60Hz)1 Phase, 208/230 V
Total Power Consumption2.9 kW*
Current Consumption12.5 amps*
Recommended Fuse Size20 amps
NEMA Plug Configuration6-20P
Min. - Max. Voltage198 - 253 V

Fans

Motor Output 0.56 kW*

Evaporator

Fan TypeCentrifugal
Max Air Flow - High/Mid/Low650/600/530 CFM*
Max. External Static Pressure0.5 IWG

Condenser

Fan TypeCentrifugal
Max Air Flow High/Mid/Low870/760/740 CFM*
Max. External Static Pressure0.16 IWG

Compressor

TypeHermetic Rotary
Output @ 230V1.5 kW

Refrigerant

TypeR-410A

Dimensions

W x D x H22 x 27 x 51 in

Weight

Net / Shipping 205 / 243 lb

Power Cord

Gauge12 AWG (3-core)
Length6 ft

Condensate Tank

Capacity5 gal

Operating Conditions

Min. - Max.65°F @ 50% RH - 95°F @ 60% RH

Max. Duct Length

Per Cold Duct Hose50 ft
Hot Duct Hose45 ft

Max. Sound Level

With Condenser Duct - High/Mid/Low66/64/61 dB(A)
Without Condenser Duct - High/Mid/Low68/66/63 dB(A)

*Specification information shown with 230 V.

Specifications subject to change without notice. All models feature compressor overload relay and fan motor protection. All models also feature compressor short-cycle protection, return air thermostat, automatic restart and accommodate a condensate pump kit. All portable models are 50 Hz-compatible with a slight performance decrease from specifications listed.


Benefits

  • Modest power usage. Runs on 208/230V 20 amp circuit and consumes 2.9 kW.
  • Cooling support effective in conditions from 65° to 95°F.
  • Moderately quiet. At highest speed with condenser duct, sound level 66 dB(A) — similar to sound levels for conversation.

Other Documents