Portable Cooling Contact: 508.460.0904 x3

Electronic Features
Control Panel
Programmable
Thermostat Control Electronic
Cooling Capacity
Rating Conditions: 95F at 60% RH
60,000 Btu/h
Electrical Characteristics
Voltage Requirement
1 Phase, 208/230V
Total Power Consumption 6.6 kW
Current Consumption 29 amps
Recommended Fuse Size 50 amps
NEMA Plug Configuration 6 – 50
Min. Max. Voltage 198 – 250
Fans
Motor Output
0.5/0.33 kW Evap.
1.2/0.93 kW Cond.
Evaporator
Fan Type
Centrifugal
Max Air Flow high/low 1940/1770 CFM
Max External Static Pressure 0.9 IWG
Condenser
Fan Type
Centrifugal
Max Air Flow high/low 2830/2650 CFM
Max External Static Pressure 0.85 IWG
Compressor
Type
Hermetic Rotary
Output 3.9 kW
Refrigerant
R-410A
3.97 lb
Dimensions
W x D x H
30 x 52 x 64 in
Net Weight/Shipping Weight
623/753 lb
Power Cord
Gauge
6 AWG (3 – core)
Length 6 ft
Condensate Tank Capacity
Auto Pump Included
Operating Conditions
Min. Max. (@ 50% RH)
65° – 105°F
Max. Duct Length
Per Cold Duct Hose
40 ft
Hot Duct Hose 100 ft
Max. Sound Level
With Condenser – Duct high/low
69/67 dB(A)
Without Condenser – Duct high/low 71/69 dB(A)